Centrifugal fan F300
F300 centrifugal fan for smoke extraction.
Description: F300 induction fan for smoke extraction. Centrifugal induction fans used to evacuate smoke and toxic gases produced as a result of a fire.
F300 series fans are designed to operate in high fire risk areas (eg tunnels, underground parking lots) for normal ventilation (carbon monoxide exhaust) and smoke and hot gas exhaust in case of fire.
These fans are F300 certified in accordance with the European standard EN 12101-3 for operation inside hazardous areas.
The fans have electrolytically galvanized sheet steel housing, dynamically balanced sheet steel propellers, suction protection grille, mounting brackets, respectively high temperature resistant service switch.
The electric motor is asynchronous three-phase with two speeds, insulation class H, degree of protection IP55, suitable for continuous operation at a maximum temperature of 50 C, respectively in an intervention regime of two hours at a maximum temperature of 300 C.